A flame sensor with carbon on it sure can. The RHEEM and York units are notorious for that very symptom. Its the first thing I look at on a no heat service call for a 90's model RHEEM

There is no reason to pounce on my post. Your one of the few here I thought / think actually knows what they are talking about. That being said, I ( like you ) think the unit in question is much older then that tech. prolly so old that it has one heck of a crack in the exchanger and is pouring CO in the home. Who knows. The OP didnt provide much info and for all I know he knows just enough to get himself into a heap of trouble. Wasn't it just last month an entire family in Catoosa almost died from CO poisoning?
A flame dirty flame sensor can cause a furnace to light and go back off on a call for heat because the flame wasn't detected. Then it retrys until lock out. Not what the op described as happening. He said it randomly turns on for a minute and shuts off and other wise heats normally.

I meant that earlier post as good natured ribbing because I believe you are on the wrong track and made your comment about people not knowing what they are talking about. you seem like good guy and always try to help people here and that makes you ok in my book
 

SPDguns

Sharpshooter
Supporting Member
Special Hen Supporter
Joined
Feb 20, 2011
Messages
5,485
Reaction score
5,679
Location
Stillwater
Wow. Lots of good info. To answer questions- It is an older Lennox. It has been doing it for several years, If it was a CO problem I would be dead and you would have read about me in the news. I'm in Stillwater. It's not a thermocouple. I'm going to hire a professional after I make an educated guess to narrow down the problem so they won't tell me "Your furnace is so old........". It's probably a pressure switch problem or moisture in a pressure switch hose. I'm going to call eaglejrs later today. I have one day off this week, Sunday and I will look at it and go from there. If I'm not dead. Other than that-----
IMG_1615.jpg
 

oneof79

Sharpshooter
Special Hen
Joined
Feb 2, 2008
Messages
1,435
Reaction score
0
Location
Moore
Older Lennox furnaces used several fan/limit schemes. 2 wire, 4 wire, 6wire. The 6 wire fan limit had a heater built in to the switch that helped with timing. A way out of adjustment heat anticipator in the thermostat could cause similar issues.
 